| Description |
| Inspection |
|
| 1. | Turn the ignition switch OFF. |
| 2. | Install the refrigerant recovery/recycling/charging system. (Refer to Air Conditioning System - "Repair procedures") |
| 3. | Turn ON the ignition switch, put into operation the air conditioner. |
| 4. | Calculate the reference voltage of the Recovery/Recycle/Recharge machine high pressure value using the formula below.
|
| 5. | Measure the sensor output voltage between terminal "1" and "2".
|
| 6. | If the reference voltage value and the sensor output voltage value are close to each other, the air conditioner pressure transducer is normal. |
| 7. | If 0V is output or the reference voltage value and sensor output voltage value are not close to each other, replace the air conditioner pressure transducer.
|
| Replacement |
| 1. | Disconnect the negative (-) battery terminal. |
| 2. | Recover the refrigerant with a recovery/charging station. |
| 3. | Disconnect the A/C pressure transducer connector (A).
|
| 4. | Remove the A/C pressure transducer (A).
|
| 5. | To install, reverse the removal procedure.
|
Repair procedures Replacement1.Remove the condenser.2.Remove the cap (A) on the bottom of the condenser with a L wrench. Tightening torque : 9.
Description and operation DescriptionThe evaporator temperature sensor will detect the evaporator core temperature and interrupt compressor relay power in order to prevent evaporator from freezing by excessive cooling.
Description and operation DescriptionThe temperature control actuator is located at the heater unit. It regulates the temperature by the procedure as follows. The signal from the control unit adjusts the position of the temperature door by operating the temperature switch.
C